0212 220 10 17 Kurumsal Çözüm Ortağınız

RE-2Y(St)HSWAH-PIMF

Indoor environments intensely populated by people where there is electromagnetic interference. Instrumentation and control engineering analog and digital signal transmissi...

  • Indoor environments intensely populated by people where there is electromagnetic interference.
  • Instrumentation and control engineering analog and digital signal transmission
  • Petroleum refineries
  • Petrochemistry industry
  • Power plants
  • Natural gas pump stations
  • Dry-moist and wet places, at indoor
  • Gas Stations
  • Water Conveyance Systems

NOTES

  • EMC*: Electromagnetic compatibility
  • Ral 5015 blue sheath*: In explosive and flare up places as ex-proof connecting, intrinsically safe
  • Ral 9005 black sheath*: Places where UV resistance is required
  • Ral 7001 grey sheath*: Inside of buildings

Conductor IEC 60228 / DIN VDE 0295 / EN 60228
Insulation EN 50290-2-23 PE COMPOUND
Colour Code BS 5308-1 OR BLACK-WHITE
EACH PAIR NUMBERED
Individual Screen PES TAPE; TINNED DRAIN WIRE;
AL-PES TAPE
Stranding PAIRWISE, SCREENED PAIRS IN LAYERS
Wrapping PES TAPE
Overall Screen TINNED COPPER DRAIN WIRE; AL-PES TAPE
Inner Sheath EN 50290-2-27 LSZH COMPOUND
Armour GALVANIZED ROUND STEEL WIRES
Sheath EN 50290-2-27 LSZH COMPOUND
Sheath Colour RAL 5015* BLUE; RAL 9005* BLACK;
RAL 7001* GREY